MacConnection Clearance Center. Shop Now!

MacConnection Interactive eCatalog


          APC Galaxy 3500 10kVA 208V w (2) Battery Modules, Start-up 5X8

          More From: APC
          Item #: 17785393
          Mfr. Part#: G35T10KF2B2S
          Availability: Temporarily Out-of-Stock
          Est. Ship: Call for next available delivery

          • Provides 10000VA, 8000watt(s), 208V power
          • Surge Suppression is Standard
          • Connector(s): Power Hard Wire 4-wire (3PH + G), Power Hard Wire 5-wire (3PH + N + G), Terminal block (clamp)
          • 3 Outlets
          • 18.8 minute(s) Battery Runtime at Full Load
          • Attributes include Double conversion online

          Ordering Information

          The MGE Galaxy 3500 offers centralized 3-phase power protection with the reliability of the MGE product family. Ideal for commercial and technical facilities as well as industrial applications, the MGE Galaxy 3500 includes dual-mains input, automatic and maintenance bypasses and scalable runtime with hot-swappable batteries for increased availability. The parallel capability for redundancy and capacity, new optional bypass panels and extended run battery frames provide increased flexibility.

          Low cost of ownership is achieved through best-in-class efficiency and a reduction in rating of electrical infrastructure - wires, transformers and generators. The built in Network Management Card with temperature monitoring provides remote monitoring and management through a simple Web/SNMP interface. Serviceability is greatly enhanced by user-replaceable batteries, front access servicing and included start-up service for maximized configurabililty. All these features make the MGE Galaxy 3500 the easiest UPS in its class to deploy, manage and maintain.
          Collapse & Return to Top
          Actual Weight 873.00 lb(s)
          Compatibility Notes Communications & Management

          Interface Ports: DB-9 RS-232, G35T
          Pre-Installed SmartSlot Card: AP9631


          Protection Class: NEMA 12, IP 51
          Regulatory Approvals: cUL Listed, CSA, CSA C22.2 No. 107.1, ISO 14001, ISO 9001, UL 1778
          # Ports 3
          Communication Interface Ethernet
          Connector Power Hard Wire 4-wire (3PH + G), Power Hard Wire 5-wire (3PH + N + G), Terminal block (clamp)
          Contents UPS, battery & power modules (installed), bolt down brackets, software CD, network management card, Smart UPS signalling RS-232 cable, start-up service, documentation
          Attributes Double conversion online
          Color Black
          Form Factor External
          Physical Dimensions 58.7"h x 14"w x 33"d
          Ports/Connectors Output Connections: (1) Hard Wire 4-wire (3PH + G); (1) Hard Wire 5-wire (3PH + N + G); (1) Screw Terminals
          Input Connection: Hard Wire 5-wire (3PH + N + G)
          Battery Run Time (max) 18.8 minute(s)
          Power Provided 10000 VA, 208 V, 8000 watt(s)
          Surge Suppression Standard
          Power Notes Output

          Output Power Capacity: 8000W/10kVA
          Maximum Configurable Power: 8000W/10kVA
          Nominal Output Voltage: 120V, 208V, 208V 3PH
          Output Voltage Note: Configurable for 200, 208 or 220V 3-phase nominal output voltage
          Efficiency at Full Load: 93.2%
          Output Voltage Distortion: Less than 3%
          Output Frequency (sync to mains): 57 - 63Hz for 60Hz nominal
          Crest Factor: Unlimited
          Topology: Double Conversion Online
          Waveform Type: Sine wave
          Output Voltage THD: < 2% linear load and < 4% non-linear load
          Efficiency at Half Load: 91.7%
          Bypass: Built-in Maintenance Bypass, Built-in Static Bypass


          Nominal Input Voltage: 208V 3-phase
          Input Frequency: 40-70Hz (auto sensing)
          Input voltage range for main operations 160 - 240V

          Batteries & Runtime

          Battery Type: Maintenance-free sealed Lead-Acid battery with suspended electrolyte, leakproof
          Included Battery Modules: (2)
          Typical recharge time: 5 hours
          Typical Backup Time at Half Load: 48.6 minutes (4000 Watts)
          Typical Backup Time at Full Load: 18.8 minutes (8000 Watts)
          Compliant Standards CSA, CSA 22.2, CUL, ISO 14001, ISO 9001
          UNSPSC 39121011
          Warranty - Labor 1 Year
          Warranty - Parts 1 Year
          Collapse & Return to Top

          Our Accessibility Policy

          We endeavor to make our website accessible to any and all users. Please contact us toll-free at 800-998-4388 if you need assistance with navigating our blog, website, or placing an order. We appreciate your business and are happy to answer any questions that you may have.